Knowledge fuels change - Support energypedia!
For over 10 years, energypedia has been connecting energy experts around the world — helping them share knowledge, learn from each other, and accelerate the global energy transition.
Today, we ask for your support to keep this platform free and accessible to all.
Even a small contribution makes a big difference! If just 10–20% of our 60,000+ monthly visitors donated the equivalent of a cup of coffee — €5 — Energypedia would be fully funded for a whole year.
Is the knowledge you’ve gained through Energypedia this year worth €5 or more?
Your donation keeps the platform running, helps us create new knowledge products, and contributes directly to achieving SDG 7.
Thank you for your support, your donation, big or small, truly matters!
Difference between revisions of "Solar Systems - Wiring and Fitting"
***** (***** | *****) m |
***** (***** | *****) m |
||
| Line 9: | Line 9: | ||
Like other electric components, accessories (particularly cables) cause losses. Since energy is expensive, these should be minimized. The power loss within a copper wired cable depends on the current I, the cable length L (back and forth) and the cross-section A of the wire as follows: | Like other electric components, accessories (particularly cables) cause losses. Since energy is expensive, these should be minimized. The power loss within a copper wired cable depends on the current I, the cable length L (back and forth) and the cross-section A of the wire as follows: | ||
| − | ΔP [W] = 0.018 | + | ΔP [W] = 0.018 x I² [A²] x L [m] / A [mm²] |
'''''Example:'''''<i>For a generator current of 5 A and a cable of 1.5 mm</i>''2 'with a length of 10 m (oneway) the power loss will be 0.018 ''∗ ''(5 A)'2''∗ ''(2''∗''10 m) / 1.5 mm''''2 ''''= 6 W In a 12 V system, this would be 10% of the whole generator power.'' | '''''Example:'''''<i>For a generator current of 5 A and a cable of 1.5 mm</i>''2 'with a length of 10 m (oneway) the power loss will be 0.018 ''∗ ''(5 A)'2''∗ ''(2''∗''10 m) / 1.5 mm''''2 ''''= 6 W In a 12 V system, this would be 10% of the whole generator power.'' | ||
| Line 15: | Line 15: | ||
Losses can be reduced by increasing the '''cross-section '''of wires or by '''higher voltage '''levels. Keep the losses in the generator circuit as well as in the load circuits below 5% (better: 3%) and in the controller- battery circuit below 0.5%. The necessary cross-section of the cable is | Losses can be reduced by increasing the '''cross-section '''of wires or by '''higher voltage '''levels. Keep the losses in the generator circuit as well as in the load circuits below 5% (better: 3%) and in the controller- battery circuit below 0.5%. The necessary cross-section of the cable is | ||
| − | A [mm] = 0.018 | + | A [mm] = 0.018 x I x L / U / 0.05 (=5%) |
Use appropriate outdoor cables to connect the modules, protect them against sunlight and damage (e.g. by rodents) and lay cablesin conduits where appropriate. | Use appropriate outdoor cables to connect the modules, protect them against sunlight and damage (e.g. by rodents) and lay cablesin conduits where appropriate. | ||
[[Category:Solar]] | [[Category:Solar]] | ||
Revision as of 08:58, 25 June 2009
Many system failures are caused by unsuitable or improperly installed cables, connectors, switches or sockets. Their current, voltage and power ratings should be in line with the system characteristics.
Unlike AC, in DC systems switching the poles (+) and (-) will cause problems. The application of special DC fittings is recommended. Otherwise, high-quality AC items should be applied. The current ratings of AC-switches can be applied only for 12 V/ 24 V DC systems. In high-voltage DC systems, they have to be higher.
The current drawn by an appliance or circuit can be calculated by dividing the power rating by the system voltage.
Example:A 1 kW inverter in a 24 V system will draw a current of 42 A (1,000 W / 24 V). Add safety margins and take overload capacity into account.
Like other electric components, accessories (particularly cables) cause losses. Since energy is expensive, these should be minimized. The power loss within a copper wired cable depends on the current I, the cable length L (back and forth) and the cross-section A of the wire as follows:
ΔP [W] = 0.018 x I² [A²] x L [m] / A [mm²]
Example:For a generator current of 5 A and a cable of 1.5 mm2 'with a length of 10 m (oneway) the power loss will be 0.018 ∗ (5 A)'2∗ (2∗10 m) / 1.5 mm'2 '= 6 W In a 12 V system, this would be 10% of the whole generator power.
Losses can be reduced by increasing the cross-section of wires or by higher voltage levels. Keep the losses in the generator circuit as well as in the load circuits below 5% (better: 3%) and in the controller- battery circuit below 0.5%. The necessary cross-section of the cable is
A [mm] = 0.018 x I x L / U / 0.05 (=5%)
Use appropriate outdoor cables to connect the modules, protect them against sunlight and damage (e.g. by rodents) and lay cablesin conduits where appropriate.